Hi-lume and Eco-10 (ECO-series) 
Single Source Controls

Tu-Wire Single Source Controls

Eco-10 (TVE) Single Source Controls

Ballast Specifications
Power Factor >.95
Ballast Factor >.85
Total Harmonic Distortion <10% (Hi-lume and Eco-10)
<20% (Hi-lume Compact and Tu-Wire)
Sound Rating Inaudible in 27dB ambient
Lamp Flicker None visible
Frequency of Operation >25 KHz (Hi-lume and Eco-10)
>42 KHz (Tu-Wire)
Inrush Current <10X operating current
Fusing Internal
Min Starting Temp 10° C
Max Case Temp 75° C

Application Notes

New fluorescent lamps must be operated for 100 hours at full output ("seasoned") to achieve proper dimming performance and average rated lamp life.

Use only rapid start type sockets with quality knife-edge contacts.

Lead length from ballast to socket must not exceed 7' (2 m) for T5HO and T12 lamps, and 3' (1 m) for T5 twin tube and T4 compact lamps.

Specification Submittal Sheets

The following Specification Submittal Sheets are available.

Ballasts for Other Voltages

The following Lutron Eco-10 (TVE-Series) 0-10VDC Dimming Ballasts are available for 347V operation:

Lamp
Type

Watts/
Length
Lamps per
Ballast

Model Number

Ballast Current

T8

32W / 48": 1 TVE-T832-347-1 .10
2 TVE-T832-347-2 .19

Selected Hi-lume and Eco-10 models are also availalble for 100/200V and 220-240V operation; consult factory.

Complete specifications are online at Ballast Specifications.

How the Eye Perceives Light

Light as it is measured is different from light as it is perceived.  For example, 1% measured light is perceived as 10% light by the human eye, and 10% measured light is seen as 32% light.  Because the eye works this way naturally, less lighting can be used.  This means dimming can create significant energy savings.