| FADEDIM | Fade a dimmer |
Syntax
FADEDIM, <intensity>, <fade time>, <delay
time>, <address 1>, ..., <address n>
| Parameter | Description | Format |
| intensity | target intensity for specified dimmer | 0 - 100 (percent) |
| fade time | time for dimmers to fade from current intensity to target intensity | HH:MM:SS example: 00:00:05 for 5 seconds see time formatting description if omitted, time defaults to 0 seconds |
| delay time | time for dimmers to delay before starting to fade | HH:MM:SS example: 00:00:05 for 5 seconds see time formatting description if omitted, time defaults to 0 seconds |
| address | system address of dimmer to fade | [processor : link :
address] maximum of 10 address per command see device address formatting description |
Description
Fades one or more system dimmers to a target
intensity using a specified fade time and after a specified delay
time.
Example
Fade processor 1, link1, MI address 0, RPM module 2,
zone 3 and processor 2, link 4, D48 address 1, Vareo Bus 4, Vareo
address 1 to 100% with a 1 second fade time and a 2 second delay
time
L232> FADEDIM, 100, 1, 2, [1.1.0.2.3], [2.4.1.4.1]
See Also
FLASHDIM
- Flash a system dimmer
STOPFLASH -
Stop flashing a system dimmer
RAISEDIM - Raise
a system dimmer
LOWERDIM - Lower
a system dimmer
STOPDIM - Stop a
dimmer raise/lower