FRPM Fade an RPM zone

Syntax
FRPM, <intensity>, <fade time>, <delay time>, <address 1>, ..., <address n>

Parameter Description Format
intensity target intensity for specified zones 0 - 100 (percent)
fade time time for zones to fade from current intensity to target intensity HH:MM:SS
example: 00:00:05 for 5 seconds
see
time formatting description
if omitted, time defaults to 0 seconds
delay time time for zones to delay before starting to fade HH:MM:SS
example: 00:00:05 for 5 seconds
see
time formatting description
if omitted, time defaults to 0 seconds
address system address of zones to fade [processor : link : address]
maximum of 10 address per command
see
device address formatting description

Description
Fades one or more RPM zones to a target intensity using a specified fade time and after a specified delay time

Example
Fade processor 1, link1, MI address 0, RPM module 2, zone 3 to 100% with a 1 second fade time and a 2 second delay time

L232> FRPM, 100, 00:00:01, 00:00:02, [1:1:0:2:3]

See Also
FV - Fade Vareo Dimmer