| SVS Monitor String | Sivoia Scene Command Monitor Output String |
Syntax
SVS, <address>, <scene command>, <status>
| Parameter | Description | Format |
| address | system address of Sivoia control that changed | [processor : link :
address] see device address formatting description |
| scene command | Sivoia scene command | 1 = Preset 1 2 = Preset 2 3 = Preset 3 R = Raise L = Lower C = Close o = Open S = Stop |
| status | current status of the scene command | STOPPED or MOVING |
Description
The SVS monitor string is output from a processor when a Sivoia changes
scene commands.
Example 1
Someone selects Preset 1 on the Sivoia controlled by processor 1, link
6, Sivoia control address 3.
SVS, [01:06:03], 1, MOVING
When the same Sivoia stops at Preset 1.
SVS, [01:06:03], 1, STOPPED
Example 2
Someone selects the raise command on the Sivoia controlled by processor 1, link
6, Sivoia control address 3.
SVS, [01:06:03], R, MOVING
When the same Sivoia stops raising.
SVS, [01:06:03], S, STOPPED
See Also
SVBP Monitor String
SVBR Monitor String
SVBH Monitor String
SVBDT Monitor String
KBMON - Keypad/Sivoia control button monitoring on
KBMOFF - Keypad/Sivoia control button monitoring off