Architectural
Motorized Group Controllers
Section
12491
PART
1 GENERAL
1.01
SUMMARY
The following specifications detail the minimum performance
and related criteria for Motorized Window Treatment Control System proposed for
this project. Any deviations from this specification must be documented in
writing and submitted to the Architect prior to the issuance of any contracts
and must also include all associated cost savings or additions, including but
not limited to equipment, equipment installation, power wiring labor and
materials, programming, documentation and project management.
A. SECTION
INCLUDES
Provide,
install and test an architectural Group Controller as specified herein for the
areas indicated on the drawings, specifications and load schedule(s).
Section 16150 (Wiring Devices/Lighting
Controls)
Section 12490 (Window treatments)
1.02
REFERENCES
Underwriters Laboratories Inc.
ISO 9001 Quality Standard
Canadian Standards Association
American National Standards Institute
Institute of Electrical and Electronic
Engineers
1.03
SYSTEM DESCRIPTION
System shall consist of 120V-60Hz motor group controller and
low voltage wallstations. System shall provide 120V-60Hz window treatment
control capability. Additional items may also be required and are described
herein and/or shown on the drawings.
1.
04 SUBMITTALS
1.05
APPROVALS
1.06
QUALITY ASSURANCE
1.07
PROJECT/SITE CONDITIONS
1.08
WARRANTY
The manufacturer shall provide a one-year limited warranty
on all equipment supplied. The warranty shall cover 100% of the cost to repair
any or replace any parts required over the first year, which are directly
attributable to the manufacturer. Warranty coverage shall begin three months
from date of delivery.
1.09
MAINTENANCE
The manufacturer shall make available to the end user a
method of ordering new equipment for expansions, replacement, or parts to be
used as spares twenty-four hours a day, seven days a week. The manufacturer
must make available new or remanufactured parts for a minimum period of ten
years from the final date of commissioning.
PART
2 PRODUCTS
2.01
ACCEPTABLE MANUFACTURERS
2.02 AC MOTOR
GROUP CONTROLLER
A. GENERAL
1. The
Group Controller shall provide open, close, and stop operation of up to two
120V-60Hz motorized window treatments.
2. The
Group Controller shall be capable of being controlled via dry contact closure
inputs.
3. The
Group Controller shall be capable of receiving either momentary or maintained
dry contact closure inputs. This
function shall be configurable by a switch.
4. The
Group Controller shall be capable of individual zone control and/or master
control from the contact closure inputs.
5. Stopping
the motor shall be accomplished either by providing a dry contact closure to
the “Stop” terminal or by applying contact closures to the “Open” and “Close”
terminals simultaneously.
6. The
Group Controller shall provide means for reversing motor direction for a given
input in the event of a miswire without removing power from the unit. The motor direction shall be configurable by
a switch.
7. The
Group Controller shall provide local override buttons that activate the window
treatments for wiring verification.
8. The
Group Controller shall provide LED indication as to the last state of the
window treatment.
B. MECHANICAL
1. The
Group Controller shall be housed in a metal enclosure capable of being surface
mounted in any orientation.
2. The
enclosure shall have separate, isolated wiring compartments for line voltage
wiring and Class 2 wiring.
3. The
Group Controller shall provide individual terminals for each neutral for mains
input and each motor.
4. The
Group Controller shall provide a grounding bar to land each ground of mains
input and each motor.
5. The
Group Controller shall provide keyed mounting features so that mounting screws
do not need to be removed.
C. ELECTRICAL
1. The
Group Controller shall operate at 110 to 127 VAC, 50 Hz or 60 Hz. Voltages are referenced to Neutral.
2. Each
channel on the Group Controller shall be rated for 5 amperes, ¼ hp motor load
at 120 VAC, 60Hz with a lifetime greater than or equal to 10,000 cycles.
3. The
Group Controller shall contain non-volatile memory that prevents system
programming to be lost in the event of power failure.
4.
The Group Controller shall meet IEC
801-2, tested to withstand 15kV electrostatic discharge without damage or loss
of memory.
5.
The Group Controller shall meet
ANSI/IEEE Std. C62.41-1980, tested to withstand voltage surges of up to 6000V
and current surges of up to 200A without damage or loss of memory.
2.11 SOURCE QUALITY CONTROL
A. Equipment
shall be 100% tested for proper operation at end-of-line prior to shipment from
the factory. Manufacturers sampling at end-of-line shall not be acceptable.
PART
3 EXECUTION
3.01
INSTALLATION
A. Equipment
shall be installed utilizing manufacturer's catalogue cut sheets and
installation instructions and in accordance with these specifications.
B. Contractor
shall furnish all equipment, labor, system setup and other services necessary
for the proper installation of the products/system as indicated on the drawings
and specified herein. System setup shall include defining each dimmer's load
type, assigning each load to a zone and setting the control functions.
3.02 FIELD QUALITY CONTROL
A. MANUFACTURERS'
FIELD SERVICES
1. Manufacturer
shall provide toll-free technical support hotline 24 hours per day, 7 days per
week.
2. Manufacturer
shall be capable of providing on-site service support within 24 hours anywhere
in the continental U.S.A., and within 72 hours anywhere in the world, except
where special visas are required.
3. Manufacturer
shall offer a renewable service contract on a year to year basis which will
include parts and factory labor as well as annual training visits.