Lutron Viseo CSI Specification 2.0x LCD-Based Lighting Control Wallstation A. LCD-based wallstations shall be Lutron Viseo Wallstation Controls. B. Control must be capable of accepting software enhancements without the need for hardware modifications C. LCD screen must provide 320x240 pixels of resolution. Contrast and backlight brightness must be adjustable. D. Control must automatically configure itself upon installation with all building zone names, scene names, area names, scene intensities, fade times, delay times, and timeclock status from preprogrammed information from system processor. ? Control will display zone names, scene names, and area names in English, French, Spanish, Dutch, German, Italian, or Portuguese if user enters this information into the processor. ? Control menus and help screens can be displayed in English, French, Spanish, Dutch, German, Italian, or Portuguese. E. Control must be capable of accessing every area, scene, and zone within the associated architectural lighting control processor. Controller must allow user to: ? view and modify the scene status of an area. ? temporarily modify zone intensities in an area. ? view timeclock status for all areas. ? enable or disable timeclock for an area. ? permanently modify zone intensities, zone delay times, and zone fade times in an area via online or offline programming. Scene programming must be accomplished without the use of an "enter" or "store" button. Programming may be accomplished either online or offline. - Online programming -- Allows scene programming via real-time adjustment of lighting zones. Lighting levels change during on-line programming. - Offline programming -- Allows for scene adjustments that are previewed via numeric intensities and bargraphs. Lights in space shall not change during off-line programming. F. If power to lighting control system is lost, LCD-based control must automatically update when power is restored. Light levels in area where power to system processor is lost shall not change or turn off as a result. G. Control shall have several configuration options for each area. Each option limits user access to the system. Each area shall be configurable to any of the following access levels from the control: ? Hidden (can not be selected for the control’s default area) ? Monitor only ? Change scenes ? Programmable H. Control programming and setup configuration may be restricted via user-modifiable numeric passcode. October 11, 2001